Parameters Setting Table
Note: “○”:The parameter can be modified in both standby and operating status.
“●”: The parameter can’t be modified in operating status
“◎”: The parameter is the actual detected and recorded value which can’t be modified.
U0 Basic Function Parameters Group
Function Code Description Set range Unit Default Modification Level Note
U0-00 Pressure set 0.5~60 Bar 3.0 ○
U0-01 Start pressure set 0-U0-00 Bar 2.4 ○ Wakeup from standby when pressure is lower than PID set pressure
U0-02 Running Direction 0:Forward
1:Reverse
2: Forbidden 0 ○ Rotation direction can be changed or stopped by modifying the parameters
U0-03 Sensor feedback type 0: (0-10)
1: (4-20)
5: (4-20)
V
mA
mA
1 ● 0: V terminal
1: C terminal
5: C1 terminal
U0-04 Sensor range 0.0-60 Bar 10 ○
U0-05 Pressure calibration factor (0~2.000) 1.000 ○ Display pressure is lower than actual pressure,increase the factor,on the contrary,decrease the factor
U0-06 Water leakage Factor 0: Close
0.0~100 Bar 1.5 ○ The larger the leakage,the smaller the factor
U0-07 Detection Time Of Maintaining Pressure 3-6000 S 30 ○
U0-08 Sleep Frequency 0.00-100 Hz 30.00 ●
U0-09 Acceptable Pressure Deviation 0-10.0 0.5 ○
U0-10 Start and Stop controlling Mode 0:keypad
1:Terminal
2:Communication control 0 ○
U0-11 restart when Power is on 0: Invalid
1: Restart when power on 1 ○
U0-12 Auto-start delay 0.1-100.0 S 10.0 ○
U0-13 Frequency given 0:U0-14
1:PID
2:Communication(slave comm.2)
3.external controller (0-10v)
4.external controller(4-20mA)
5.C1 (4-20mA) 1 ○
U0-14 Hand input frequency 0.00-200 Hz 50.00 ○
U0-15 Max.Frequency 5.00-200 Hz 50.00 ●
U0-16 Upper limit Frequency 5.00-200 Hz 50.00 ●
U0-17 Lower limit Frequency 5.00-50 Hz 0 ●
U0-18 Acceleration Time 0.1-6000 S 4.0 ○
U0-19
Deceleration time
0.1-6000
S
4.0 ○
U0-20 Stop Method 0: Stop by deceleration
1: Natural Stop 0 ○
U0-21 Reserve ----- ---- ○
U0-22 Parameters Initialization 0-9999 0 ● 11: Reset to factory setting
22:Remove faults
U1 Pump Parameters Group
Function Code Description Set range Unit Default Modification Level Note
U1-00 Water Shortage Detection Options 0: Do not detect
1:By current
2:By Press.
3:By current & press.
4:Water shortage 2 when U1-00=4, U2-10 must be set 11
U1-01 Water Shortage Detecting Pressure 0-60.0 Bar 0.5 ○
U1-02 Water Shortage Detecting Frequency 0.00-100.0 Hz 45.00 ○ Only detecting water shortage when running frequency is over set frequency
U1-03 Delay Time For Water Shortage Detection 0.1-999.9 S 50.0 ○
U1-04 Detecting Current For Water Shortage Depending on motor type A ○ Applicable for U1-00:1&3
U1-05 High Pressure Alarm Value 0-60.0 Bar 15.0 ○
U1-06 Detection Time For High Pressure Alarm 0.0-200.0 S 3.0 ○
U1-07 Low Pressure Alarm Value 0-60.0 Bar 0 ○
U1-08 Detection Time For Low Pressure Alarm 0.0-6000.0 S 60.0 ○
U1-09 Anti-Freezing Function 0: OFF
1: ON 1 ○
U1-10 Running cycle for anti-freezing 3-60000 Min 1500 ○
U1-11 Running Time For Anti-Freezing 0-6000 S 10 ○
U1-12 Anti-Freezing Running Frequency 0.00-100.00 Hz 30.00 ○
U1-13 Times of alarm auto reset 0-1000 200 ○
U1-14 Alarm auto reset time 0-60000 Min 10 ○
U1-15
Alarm reset command
0:OFF
1:ON 111 ●
U2 Input & Output Parameters Group
Function Code Description Set Range Unit Default Modification Level Note
U2-00 Min.Input V value 0.00-10.00 0.00 ○
U2-01 Frequency For Min.Input V Value 0.0-100.0 % 0.00 ○
U2-02 Max.Input V Value 0.00-10.00 10.00 ○
U2-03 Corresponding Frequency For Max.Input V Value 0.0-100.0 % 100.0 ○
U2-04 V Filter Time Constant 0.01-10.00 s 0.05 ○
U2-05 Min.Input C Value 0.00-20.00 4 ○
U2-06 Corresponding Frequency For Min.Input C Value 0.0-100.0 % 0.0 ○
U2-07 Max.Input C Value 0.00-20.00 20.00 ○
U2-08 Corresponding Frequency For Max.Input C Value 0.0-100.0 % 100.0 ○
U2-09 C Filter Time Constant 0.01-10.00 s 0.05 ○
U2-10 DI1 Multi-functional Input Terminal 0: No function
1:Forward running
2:Reverse running
3:Fault input
4:Haste stop
5:Reset
6: PID pause
7:Command by keypad
8: Command by terminal
9: Command by communication
10:fault input when constant cose is chosen
11: Water shortage input
1 ● 11: Water Shortage Input
When D11 and GND are disconnected,water shortage alarm will be displayed on the screen.
U2-11 DI2 Multi-functional Input Terminal 0 ●
U2-12 DI3 Multi-functional Input Terminal 11 ●
U2-14 Mo output 0: No function
1: running status
2:fault
3:FD
4:FDT2
5: Zero frequency running
6:Lower limit frequency running
7:Upper limit frequency running
8:Standby
9:Sleeping
10: Reach temp. 1 ○
U2-15 Relay1 (TA,TB,TC) 2 ○ TA /TB normal closed, TA/TC open
U2-16 Relay2 (TA1,TB1,TC1) 1 ○ TA1 /TB1 normal closed, TA1/TC1 open
U2-17 Valid DI1 input delay 0.0-3600.0 s 0.0 ○
U2-18 Invalid DI1 input delay 0.0-3600.0 s 0.0 ○
U2-19 Valid DI2 input delay 0.0-3600.0 s 0.0 ○
U2-20 Invalid DI2 input delay 0.0-3600.0 s 0.0 ○ Relay TA/TB/TC
U2-21 Valid DI3 input delay 0.0-3600.0 s 0.0 ○
U2-22 Invalid DI3 input delay 0.0-3600.0 s 0.0 ○
U2-23 Mo output delay 0.0-3600.0 s 0.0 ○
U2-24 relay output delay 0.0-3600.0 s 0.0 ○
U2-25 Relay1 output delay 0.0-3600.0 s 0.0 ○
U3 Advanced Parameters Group
Function Code Description Set Range Unit Default Modification Level Note
U3-00 Baud rate for communication 5:9600
6:19200
7:38400 6 ●
U3-01 Address 3~5 for slave drive.
1,2 for master drive 1 ●
U3-02 Alternation time 0-60000 min 480 ●
U3-03 Auxiliary drive quantity 0-4 0 ●
U3-04 Multi-pump control method 0: master-slave control
1:Synchronous control 0 ●
U3-05 Pump-adding delay 0.1-600.0 s 1.0 ●
U3-06 Pump-reducing delay 0.1-600.0 s 0.1 ●
U3-07 Delay of standy master starts 0.1-30.0 s 20 ●
U3-08 Standard baud rate 5: 9600
6: 19200
7:38400 5 ●
U3-09 Standard protocol address 0-247 1 ●
U3-10 Screen Display on stop Status 0-9 204 ○ Refer to d monitoring parameters group
U3-11 The First Display Parameter Under Running Status 0-4 4 ○ Refer to d monitoring parameters group
U3-12 Carrier Frequency 1-12 6 ●
U3-13 Torque Enhancement 0-20.0 % 4.0 ● Depending on motor
U3-14 Low Frequency Vibration Suppression Intensity 0-100 100 ○
U3-15 High Frequency Vibration Suppression Intensity 0-100 0 ○
U3-16 The Turning Point Between Low & High Frequency 5.00-50.00 Hz 20.00 ●
U3-18 Protection for short circuit on ground when power on 0: closed
1: ON 1
U3-19 Sleeping Delay Time 1.0-200.0 s 10.0 ○
U3-20 1 Proportionality Factor 0.0-50.0 15.0 ○
U3-21 1 Integral Time 0.1-100.0 s 1.5 ○
U3-26 2 Proportionality Factor 0.0-50.0 s 10.0
U3-27 2 Integral Time 0.1-100.0 S 2.0
U3-28 Diviation of PID change 0-100 % 60.0
U3-30 Detect value for disconnected sensor 0.0-100.0 % 5.0
U3-31 Time for detecting disconnection of sensor 0.0-3000.0 s 10.0 ○ 0.0 represents do not recognize
U3-32 Motor type 0: asynchronous
1:Permanent magnet synchronous 0 ●
U3-33 Rated motor power 1-1000 KW ● Depending on motor type
U3-34 Rated motor speed 1-10000 rpm ● Depending on motor type
U3-35 Rated motor voltage 1-800 V ● Depending on motor type
U3-36 Rated motor current 0.1-1000.0 A ● Depending on motor type
U3-37 Rated motor frequency 5.00-200.0 Hz ● Depending on motor type
U3-38 Output phase loss protection option 0: OFF
1: ON 1 ○
U3-40 Motor overload gain protection 20.0-1000.0 % 100.0 ○
U3-41 Quick current limit 0: OFF
1: ON 1 ○
U3-42 Overvoltage (stall speed) Protection Voltage 120-150 % 130 ○
U3-43 Overcurrent Stall Speed Gain 0-100.0 s 20 ○
U3-44 Overcurrent (stall speed)Protection Current 100.0-200.0 % 160 ○
U3-45 Low Voltage Protection Current 70.0-100.0 % 100.0 ○
U3-46 Auto fault reset times 0-20 3 ○
U3-47 Fault reset Interval time 0.1-100.0 s 10.0 ○
U3-54 Sleep section 0: OFF
1:ON 1 ●
U3-55 Input phase loss protection 0: OFF
1:ON 1 ●
d monitoring parameters group
d-00: Output frequency
d-03: Temperature
d-06: Feedback pressure
d-09:Accumulated power-on time(0-65535H)
d-12:DI input
d-14:The second fault type
d-17: Current when faults happen
d-20: Fault time
d-21:Feedback pressure when faults happen d-01: Output current
d-04: Set pressure-current pressure
d-07:Set speed
d-10: V input voltage value
d-13:The first fault type
d-15:The third fault type
d-18: Bus voltage when fault occur d-02: Bus voltage
d-05: Set pressure
d-08:Accumulated running time(0-65535H)
d-11:C input current value
d-16:Fault frequency
d-19:Internal Temperature when faults happen