Frequently Asked Questions
1.When no one is using water, the machine will not hibernate and stop.
First of all, see if the feedback pressure on the right side of the interface reaches the target pressure value on the left.
If it does, first press the stop button to stop the pump manually, then observe if the feedback pressure drops.
If it falls down, check whether the pipeline is leaking, whether the water outlet is not closed, whether the check valve is back to the water, solve the above problems, the pump can naturally hibernate and stop.
2.The pump starts frequently
Firstly, turn up the set pressure
Secondly, adjust the dormant frequency of UO-08 from 30 to 20 Hz.
d Monitor parameter group (press and hold "Menu" for three seconds and "U0" appears, then press "Menu" again to enter the d parameter group)
d-00:Output frequency d-01:Output current d-02:Busbar voltage
d-03:Temperature d-09:Accumulated power-on time (0~65535H)
d-15:Third (most recent) fault type d-16:Fault frequency
d-17:Fault current d-18:Fault bus voltage
Parameter table
UO Basic function parameter groups
Function Code Function code description Setting range Unit Factory value Note
UO-00 Pressure setting 0.0~60.0 Bar 3 When using multiple pumps inline, only the main unit parameters need to be set
UO-01 Start pump pressure value 0~UO-00 Bar 2.7 below the PID set pressure value, wake up to sleep
UO-02 Operating steering 2禁止
0:正转1:反转 0 Change this parameter to change the motor
steering or 2 prohibit adjustment of steering
UO-03 Sensor feedback
Type of feedback 1: (4-20)
2:(0-5)
3 :(0.5-4.5) mA
v
V 1 4-7.5KW factory default 1:(4-20)
3 0.75-2.2KW factory default 3:(0.5-4.5)
UO-04 Sensor range 0.0~60.0 Bar 10.0
UO-05 Pressure calibration factor (0~2.000) 1.000 The displayed value is less than the actual value increase this factor, the displayed value is greater than the actual value decrease this factor
A value greater than the actual value decreases this factor
UO-07 Hold pressure check interval 3~6000 S 30 The shorter the time the faster the dormancy
UO-08 Dormancy frequency 0.00Hz~100Hz Hz 30
Function Code Function code description Setting range Unit Factory value Note
UO-09 Leakage factor 0~10.0 0.5 The larger the water leak, the greater the dormancy factor
UO-10 Start/stop command
Source selection 0: Keypad start/stop
1:Terminal start/stop
2:Communication control start/stop
UO-13 Frequency giving 0: UO-14
1:PID
2:Communications (Auxiliary Communications 2)
UO-14 Manual preset frequency o.00~200 Hz 50
UO-18 Acceleration time 0.1~6000.0 s 6 Model confirmation
UO-19 Deceleration time 0.1~6000.0 s 6
U0-22 Parameter initialisation 0~9999 11:Restore factory values
22:Clear the fault to zero
U1 Protection parameter groups
Function Code Function code description Setting range Unit Factory value Remarks
U1-00 Water shortage detection method selection 0:No detection
1:Using current
2:Use of pressure
3:Use of current
and pressure
4:Water shortage terminal 2 When set to the water shortage terminal
U2-10 to be set to 11
U1-o1 Water shortage detection pressure 0~200.0 Bar 0.5
U1-03 Water shortage detection delay time 0.1~999.9 s 90.0
U1-04 Water shortage detection current value Model confirmation A For water shortage detection methods 1 and 3
U1-09 Anti-freeze function 0:off 1:on 1
U1-13 Automatic alarm recovery times 0~1000 200
U1-14 Automatic alarm recovery time 0~60000 Min 10
U2 terminal functional parameters
Function Code Function code description Setting range Factory value Remarks
U2-10 DI1 multi-function input
input terminal 0:No function
2:Reverse 1:Forward
3:Fault input
4:Emergency stop 5:Reset
10:Normally closed fault input
11:Water shortage input 1 11: Water shortage input.When DI1 and GND Disconnected to display water shortage alarm
U2-14 Mo multifunctional output
Terminal input selection 0:No function 1:Run
2:Fault 3:FDT1
4:FDT25:Zero
6:Lower frequency operation
7:Upper limit frequency operation
8:Standby 9:Sleeping
10:Temperature reached 1
U3 Advanced Parameters Group
Function Code Function code description Setting range Unit Factory Value Note
U3-O1 Local address 3 to 5 are auxiliary machines.
1.2 for the main engine
U3-02 Wheel pump time 0~6000o Min 48o 0:No wheel pump
uU3-03 Number of auxiliary machines 0一4
u3-04 Multi-pump control mode 0:Multi-pump primary and secondary control
1:Multi-pump synchronous control
U3-05 Add pump delay time 0.1~600.o 20
U3-06 Decrease pump delay time 0.1~600.0 0.1
u3-07 Standby main unit effective delay time 0.1~60.0 5
u3-12 Carrier setting 1~12 6
U3-19 Hibernation delay time 0.1~200.0 1.o
u3-32 Motor control method 0 or 2 0:VF control of asynchronous motors
2:Synchronous motor vector control
u3-33 Motor power rating 1100o KW Model confirmation
u3-34 Motor speed rating 0一65535 RPM Model confirmation
U3-36 Motor rated current 0.1~1000.o A Model confirmation
u3-38 Fault enable selection 0~11111 11 o:disable protection 1 :enable protection
Bit 1:Motor overload Bit 10:Output phase loss
Hundred bits:input phase continuation Thousand bits:power-on short-circuit to ground
10,000 bits:run first output detection (to ground and phase loss
u3-39 Speed tracking start 0 OR 1 :direct start
1 :speed chasing synthesis start
u3-48 Stepper motor counter-electromotive force factor 0一6553.5 Machine type confirmation
u3-49 Motor self-learning parameters 0~2 0:Static 1:Static recognition 2:Dynamic recognition
u3-5o Synchronous motor stator resistance 0一65.535 Type confirmation
u3-51 Synchronous motor d-axis inductance 0一655.35 mH Model confirmation
u3-52 Synchronous motor q-axis inductance 0一655.35 mH Model confirmation
u3-53 Low-speed excitation current 0一80 10
u3-54 Dormancy selection 0:off 1:on