News

134B7209 cable clamp/d=36-40 k40b

134B6488 Panel Through Mounting kit w/o Panel, B2

134B6544 Real Time Clock D slot option MCB117 "The VLT® Real-time clock option MCB 117 option provides advanced data-

logging functionality to the following drives

VLT® HVAC Drive FC 102

VLT® Refrigeration Drive FC 103

VLT® Aqua Drive FC 202

VLT® Automation Drive FC 301/FC 302"

134B6782 Front cover with gasket for C2

134B6880 VLT Progr. Contr. MCA 301, coated

134B6883 VLT Progr. Contr. MCB 301, coated

134B7093 VLT C-option Adapter MCF 107

134B7207 cable clamp/d=44-48 k48b

134B7209 cable clamp/d=36-40 k40b

134B7466 Option A Ethernet Package

134B8814 VLT® PROFINET MCA120 coated 5pcs

134B9400 Pressure Sensor 7245T 2x500Pa & PT1000 "DUAL AIR PRESSURE SENSOR ±500PA Temperature drift: ±

0.1% per °C ⁄ °F

Zero point offset: ± 10 % of measuring range

Above- ⁄ below-pressure: max. ± 50 kPa / ± 200 inWC

Power: 24VAC (± 20%) <(><<)>0,2W / 15…36VDC

Operation temperature: –30...+70 °C / –22...+158 °F

Media temperature –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with two M16 cable glands one M12 for

temperature

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9401 Pressure Sensor 7249T 500/7000Pa &PT1000 "DUAL AIR PRESSURE SENSOR ±500PA Temperature drift: ± 0.1 % per °C #

°F

Zero point offset: ± 10 % of measuring range

Above- # below-pressure: max. ± 50 kPa / ± 200 inWC

Power: 24VAC (± 20%) <0,2W / 15…36VDC

Operation temperature: –30...+70 °C / –22...+158 °F

Media temperature –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with two M16 cable glands one M12 for

temperature

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9402 Pressure Sensor 7247T 2x7000PPa & PT1000 "DUAL AIR PRESSURE SENSOR ±7000PA Temperature drift: ± 0.1 % per °C #

°F

Zero point offset: ± 10 % of measuring range

Above- # below-pressure: max. ± 50 kPa / ± 200 inWC

Power: 24VAC (± 20%) <0,2W / 15…36VDC

Operation temperature: –30...+70 °C / –22...+158 °F

Media temperature –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with two M16 cable glands one M12 for

temperature

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9404 Pressure Sensor 7225 2x500Pa, Analog "DUAL AIR PRESSURE SENSOR ±500PA ±500PA, ANALOGUE

Dual pressure transmitter with 2x8 switchable measuring ranges and 2

automated analogue output signals in a resistant IP65 plastic housing

with quick-locking screws, connection nozzles for pressure hose (Ø 6 mm)

and a M16 cable gland for cable connection. The pressure measuring

transducer automatically detects the required output type and converts

the measurands into the required standard signal of 0–10 V or 4...20 mA.

Pressure range selection: ± 500 Pa – 0…100Pa / 200Pa / 300Pa / 500Pa

Accuracy: 500 Pa typical ± 13 Pa

Zero point offset: ± 10 % of measuring range

Above- # below-pressure: max. ± 50 kPa

Power: 24VAC/DC (± 10%) <1,3W,

Output: automatically switching 0 -10 V # 4...20 mA

Working resistance: Ra (ohms) = 25...450 Ohm (at I output)

Load resistance: RL > 15 kOhm (at U output)

Operation / Media temperature: –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with one M16 cable gland

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9405 Pressure Sensor 7229 500/7000Pa, Analog "DUAL AIR PRESSURE SENSOR ±500PA ±7000PA, ANALOGUE

Dual pressure transmitter with 2x8 switchable measuring ranges and 2

automated analogue output signals in a resistant IP65 plastic housing

with quick-locking screws, connection nozzles for pressure hose (Ø 6 mm)

and a M16 cable gland for cable connection. The pressure measuring

transducer automatically detects the required output type and converts

the measurands into the required standard signal of 0–10 V or 4...20 mA.

Pressure range selection: ± 500 Pa – 0…100Pa / 200Pa / 300Pa / 500Pa

Pressure range selection: ± 7000 Pa – 0…1000Pa / 2000Pa / 3000Pa /

5000Pa / 7000Pa

Accuracy: 500 Pa typical ± 13 Pa

Accuracy: 7000 Pa typical ± 105 Pa

Zero point offset: ± 10 % of measuring range

Above- # below-pressure: max. ± 50 kPa

Power: 24VAC/DC (± 10%) <1,3W,

Output: automatically switching 0 -10 V # 4...20 mA

Working resistance: Ra (ohms) = 25...450 Ohm (at I output)

Load resistance: RL > 15 kOhm (at U output)

Operation / Media temperature: –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with one M16 cable gland

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9406 Pressure Sensor 7227 2x7000Pa, Analog "DUAL AIR PRESSURE SENSOR ±7000PA ±7000PA, ANALOGUE

Dual pressure transmitter with 2x8 switchable measuring ranges and 2

automated analogue output signals in a resistant IP65 plastic housing

with quick-locking screws, connection nozzles for pressure hose (Ø 6 mm)

and a M16 cable gland for cable connection. The pressure measuring

transducer automatically detects the required output type and converts

the measurands into the required standard signal of 0–10 V or 4...20 mA.

Pressure range selection: ± 7000 Pa – 0…1000Pa / 2000Pa / 3000Pa /

5000Pa / 7000Pa

Accuracy: 7000 Pa typical ± 105 Pa

Zero point offset: ± 10 % of measuring range

Above- # below-pressure: max. ± 50 kPa

Power: 24VAC/DC (± 10%) <1,3W,

Output: automatically switching 0 -10 V # 4...20 mA

Working resistance: Ra (ohms) = 25...450 Ohm (at I output)

Load resistance: RL > 15 kOhm (at U output)

Operation / Media temperature: –20...+50 °C / –4...+122 °F

T2-IP65 plastic housing with one M16 cable gland

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9407 Airflow Sensor KFTF Temp & Humidity "DUCT HUMIDITY- AND TEMPERATURE SENSORS KFTF-MB

Calibratable duct humidity and temperature sensor KFTF-T3 (± 2.0%) with

Modbus RTU connection, in a resistant IP65 plastic housing with quick-

locking screws and M16 cable gland for cable connection and a plastic

sinter filter (exchangeable). Including mounting flange to detect the

relative humidity (0…100% RH) and the temperature (–35...+80 °C) inside

a tube, including various parameters in the humidity measurement. The

duct sensor is applied in a non-aggressive and dust-free environment and

is suitable for installation in ceilings, ducts and devices.

International SI units (default) can be switched to Imperial (via

Modbus).

Measuring range: 0...100 % RH (humidity) / – 35...+80 °C (temperature)

Medium: clean air and non-aggressive, non-combustible gases

Deviation, humidity: typical ± 2.0 % (20...80 % RH) at +25 °C, otherwise

± 3.0 %

Deviation, temperature: typical ± 0.2 K at +25 °C

Zero point offset: ± 10 % RH (humidity) / ± 5 °C (temperature)

Power: 24VAC (± 20%) / 15…36VDC - 24DC <1,2W

Operation temperature: –30...+70 °C / –22...+158 °F

T3-IP65 plastic housing with two M20 cable glands

Housing dimensions: 108 x 78.5 x 43.3 mm / 4.25 x 3.1 x 1.7 in"

134B9408 Airflow Sensor 8148 Temp&Humidity&500Pa "DUCT HUMIDITY-, TEMPERATURE- AND PRESSURE SENSORS ±500PA-MB

Maintenance-free duct sensor covering humidity, temperature and pressure

in one transducer. Microprocessor-controlled with Modbus RTU connection

in a resistant IP65 plastic housing with quick-locking screws and M16

cable gland for cable connection. Including mounting flange to detect

the relative humidity (0…100% RH) and the temperature (–35...+80 °C)

inside a tube, with an exchangeable plastic sinter filter. A

differential air pressure (max. ± 500 Pa) with connection nozzles for

pressure hose (Ø 6 mm). The duct sensor is applied in a non-aggressive

and dust-free environment and is suitable for installation in ceilings,

ducts and devices. International SI units (default) can be switched to

Imperial (via Modbus).

Measuring range: 0...100 % RH (humidity) / – 35...+80°C /-31… +176°F

(temperature)

Medium: clean air and non-aggressive, non-combustible gases

Deviation, humidity: typical ± 2.0 % (20...80 % RH) at +25°C/+77°F ,

otherwise ± 3.0 %

Deviation, temperature: typical ± 0.2 K at +25 °C / ± 0.4 °F at +77 °F

Pressure range: ± 500 Pa

Accuracy: 500 Pa/2.0 inWC: typical ± 13 Pa at +25 °C / ± 0.05 inWC at +

77 °F

Above- # below-pressure: max. ± 50 kPa

Power: 24VAC (± 20%) / 15…36VDC - 24DC <0,2W

Operation temperature: –30...+70 °C / –22...+158 °F

Media temperature –20...+50 °C / –4...+122 °F IP65 plastic housing two

M16 cable glands

Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"

134B9409 Airflow Sensor 8147 Temp&Humidity&7000Pa "DUCT HUMIDITY-, TEMPERATURE- AND PRESSURE SENSORS ±7000PA-MB

Maintenance-free duct sensor covering humidity, temperature and pressure

in one transducer. Microprocessor-controlled with Modbus RTU connection

in a resistant IP65 plastic housing with quick-locking screws and M16

cable gland for cable connection. Including mounting flange to detect

the relative humidity (0…100% RH) and the temperature (–35...+80 °C)

inside a tube, with an exchangeable plastic sinter filter. A

differential air pressure (max. ± 7000 Pa) with connection nozzles for

pressure hose (Ø 6 mm). The duct sensor is applied in a non-aggressive

and dust-free environment and is suitable for installation in ceilings,

ducts and devices. International SI units (default) can be switched to

Imperial (via Modbus).

Measuring range: 0...100 % RH (humidity) / – 35...+80°C /-31… +176°F

(temperature)

Medium: clean air and non-aggressive, non-combustible gases

Deviation, humidity: typical ± 2.0 % (20...80 % RH) at +25°C/+77°F ,

otherwise ± 3.0 %

Deviation, temperature: typical ± 0.2 K at +25 °C / ± 0.4 °F at +77 °F

Pressure range: ± 7000 Pa

Accuracy: 7000 Pa/28 inWC: typical ± 105 Pa at +25 °C / ± 0.12 inWC at +

77 °F

Above- # below-pressure: max. ± 50 kPa

Power: 24VAC (± 20%) / 15…36VDC - 24DC <0,2W

Operation temperature: –30...+70 °C / –22...+158 °F

Media temperature –20...+50 °C / –4...+122 °F IP65 plastic housing two

M16 cable glands

PREVIOUS:181B5027 OPT-D2-V+DLFI:SysBus(1fiber) + isol.CAN

NEXT:176F3711 Current Transformer, AAF, 500A, 3pcs

Leave a message

Facebook

Twitter

Instagram

Pinterest

LinkedIn

+86-15959950473

candice20114

whatsapp

ausenist@ausenist.com

137651048