Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"
134B9410 Wall Sensor ATM2 Temperature "OUTSIDE / WET ROOM TEMPERATURE SENSOR ATM2-MB
Calibratable outside temperature sensor ATM2, PT1000 measure temperature
(-50...+150 °C), with Modbus RTU connection, in a resistant IP65 plastic
housing with quick-locking screws and M20 cable gland for cable
connection. International SI units (default) can be changed to imperial
(via Modbus).
Sensor type: PT1000 class B (DIN EN 60751)
Measuring range: – 50...+150°C /-31… +176°F
Deviation: typical ± 0.2 K at +25 °C / ± 77 °F
Zero point offset: ± 10 °C / ± 50 °F
Ambient temperature: Measuring transducer –30...+70 °C /-22… +158°F
Medium: clean air and non-aggressive, non-combustible gases
Power: 24VAC (± 20%) / 15…36VDC - 24DC <1,2W
Operation temperature: –30...+70 °C / –22...+158 °F
T3-IP65 plastic housing with two M20 cable glands
Housing dimensions: 108 x 78.5 x 43.3 mm / 4.25 x 3.1 x 1.7 in"
134B9411 Wall Sensor AFTF Temp & Humidity "ON-WALL- HUMIDITY- AND TEMPERATURE SENSORS AFTF–MB
Calibratable outside humidity and temperature sensor AFTF, detect the
relative humidity (0…100% RH) and the temperature (–35...+80 °C),
including various parameters in the humidity measurement. Applied in
clean air and non-aggressive, dust-free environment. With a Modbus
connection in a resistant IP65 plastic housing and M20 cable gland for
cable connection, with quick-locking screws and an exchangeable plastic
sinter filter. International SI units (default) can be changed to
imperial (via Modbus).
Measuring range: 0...100 % RH (humidity) / – 35...+80 °C (temperature)
Medium: clean air and non-aggressive, non-combustible gases
Deviation, humidity: typical ± 2.0 % (20...80 % RH) at +25 °C, otherwise
± 3.0 %
Deviation, temperature: typical ± 0.4 K at +25 °C / ± 77 °F
Zero point offset: ± 10 % RH (humidity) / ± 5 °C (temperature)
Power: 24VAC (± 20%) / 15…36VDC - 24DC <1,2W
Operation temperature: –30...+70 °C / –22...+158 °F
T3-IP65 plastic housing with two M20 cable glands
Housing dimensions: 108 x 78.5 x 43.3 mm / 4.25 x 3.1 x 1.7 in"
134B9412 Airflow Sensor TF65 PT1000 Temperature "DUCT TEMPERATURE SENSOR TF 65
The TF 65 temperature measuring transducer is a PT1000 class B
resistance sensor with passive output. Measuring range from –30...+150 °
C. In a resistant IP67 plastic housing and M16 cable gland for cable
connection and a straight protective measuring tube and a mounting
flange.
Sensor type: PT1000 class B (DIN EN 60751) 1000ohm at 0°C ± 0,3 K
Measuring range: –30...+150 °C/ –22...+302 °F
Ambient temperature: –20...+100 °C / –4...+212 °F
Testing current: < 0.6 mA
Insulating resistance: 100 M#, at +20 °C (500V DC)
Connection type: 2-wire connection
Measuring tube: stainless steel, V4A (1.4571), Ø 6 mm, inserted length =
300 mm / 11.8 in
T1-IP67 plastic housing with a M16 cable glands and a mounting flange.
Housing dimensions: 72 x 64 x 37.8 mm / 2.83 x 2.52 x 1.49 in"
134B9413 Airflow Sensor KLQ CO2 & Air Quality "DUCT AIR QUALITY (VOC) AND CO2 SENSOR KLQ-CO2-MB
Maintenance-free duct sensor covering air quality (VOC 0…100 %), carbon
dioxide (CO2 0...5000 ppm) and atmospheric pressure (hPa). The air
quality is detected by a VOC sensor (mixed gas sensor for volatile
organic substances) and include an automatic calibration. It determines
the loading of the room air due to contaminated gases such as cigarette
smoke, body perspiration, exhaled breathing air, solvent vapors,
emissions etc. The air contamination can be selected into different
sensitivity ranges as low, medium or high. The CO2 measurement is
performed using an optical NDIR sensor (non-dispersive infra-red
technology), and the detection range is calibrated for standard
applications such as monitoring residential rooms and conference rooms.
A microprocessor-controlled solution with factory sensor calibration,
Modbus RTU connection in a resistant IP65 plastic housing with mounting
flange, quick-locking screws and two M16 cable gland for cable
connection. International SI units (default) can be changed to imperial
(via Modbus).
VOC Sensor: Volatile Organic Compounds sensor (metal oxide) with
automatic calibration
VOC measuring range: 0...100 % air quality; referred to calibrating gas
temperature dependence: ± 5 ppm pro °C or ± 0,5 % of measured value pro
°C (whichever is higher) pressure dependence: ± 0.13 % per mm Hg
Medium: clean air and non-aggressive, non-combustible gases
Power: 24VAC/DC (± 10%) 24DC <1,6W
Operation temperature: –10...+60 °C / 14...+140 °F
T2-IP65 plastic housing two M20 cable glands
Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"
134B9414 Antifreeze Thermostat FS20, 0/+15C "TWO-PHASE FROST PROTECTION THERMOSTATS FS-20-UW
Electronic frost protection thermostat or frost monitor with switching
relay output, continuous temperature and valve output (summation output
0–10 V) and control and cascading output (0–10 V), optionally with
connection for a heating element. A IP65 resistant plastic housing with
display with the actual temperature, measuring range,
overrange/underrange of the set switch point (frost protection
temperature) and alarm indicator for ""frost"" or ""error"" (capillary
breakage, overvoltage/undervoltage), quick-locking screws and a fully
active sensor rod made of copper. The delivery scope includes a set of
MK-05-K mounting clamps for expert attachment of the sensor rod.
Measuring range: 0...+15 °C / 32...+59 °F
Accuracy: typical ± 1 K (at +10 °C)
Sensor type: 3m Copper rod active along the entire sensor length, min.
response length of 25 cm
Input: 1 x 0 -10 V control input DDC
1 x 0 -10 V output valve (frost signal with control voltage and
cascading)
1 x potential-free changeover contact (24 V), range of adjustment 0...+
15 °C
Current consumption: max. 100 mA at 24 V DC
Load resistance: RL > 50 kOhm
Ambient temperature: –15...+50 °C / 5...+122 °F (Housing) –20...+60 °C
/ -4...+140 °F Sensor and capillary tube > 20 cm from the housing.
Power: 24VAC/DC (± 10%) 24DC <2,4W
T2-IP65 plastic housing with three-line display 70x40 mm (WxH), a M16
cable glands and MK-05-K mounting clamps.
Housing dimensions: 126 x 90 x 50 mm / 4.96 x 3.54 x 1.97 in"
134B9425 Enclosure protection in Stainl Steel V2A "WEATHER AND SUN PROTECTION HOOD
Weather and sun protection hood in stainless steel V2A, 200 x 180 x 150
mm / 7.87 x 7.1 x 5.9 in"
136B1569 Encoder/Resolver Option OC7M0
136B2055 Blind Panel OPX00
136B2082 Control panel flush mounting kit
136B2083 Control panel surface mounting kit Mounting kit for control panel - surface mounted
136B2084 Control panel cable 2.5m
136B2085 Control panel cable 5 m
136B2086 Control panel cable 10 m
136B3128 Control Panel 2.8 OPX20
136B3568 Digital 230 V AC Input OC7D0 "Digital 230 V AC Input OC7D0 which includes 5 Digital Inputs 42 – 240 V
AC"
136B3961 AAF 007 Current Transducer 2500A
136B4007 AAF 007 Current Transducer 3000A
141F1076 CHK0062N6A0 Choke 62A 690V CHK0062N6A0
141F1077 CHK0087N6A0 Choke 87A 690V CHK0087N6A0
141F4277 AS-interface Fieldbus Option, OPT-BK-V OPT-BK-V
141F4355 MR10 ED Demo unit VACON-DEM-0100-3L-5-ED-MR10
175U0009 Mounting bracket Kit, 216 x 30 x 18mm Mounting angle for flatpack resistor 200W
175U0085 Mounting bracket: Footprint, A2 Back frame A2 for 1 brake resistor
175U0086 Mount. Brack.: Footprint, A3, f.2 br.res Back frame A3 for 2 brake resistors
175U0087 Mount. Brack. Footprint, A2, f. 2 br.res Back frame A2 for 2 brake resistors
175U0088 Mounting brackets: Footprint, A1
175U0388 Mounting brackets: Footprint, K3
175Z0929 LCP Cable, 3m "Cable for control panel (LCP), 3 meters
Works with the following LCP:
Alphanumeric control panel LCP3 - 175N0131
VLT® LCP 102 Graphic Display - 130B1107
VLT® LCP 101 Numeric Display - 130B1124
VLT® LCP 102 Graphic display IP66 - 130B1078
Product group: F1"
176F1784 VLT® USB Extension
176F1841 kit, motor, f2/f4, 600mm, top entry
176F1845 kit, common motor terminals, f1/f3
176F1847 kit, rittal f-frame side cabinet, 400mm kit, rittal f-frame side cabinet, 400mm
176F1848 kit, rittal f-frame side cabinet, 600mm kit, rittal f-frame side cabinet, 600mm
176F3409 Adapter Plate, D1h/D3h VLT® drive replace adptr plate d1h d3h
176F3410 Adapter Plate, D2h/D4h VLT® drive replace adptr plate d2h d4h
176F3452 Pedestal Kit, 200mm, D5h/D6h "Sub-base kit, H 200 mm for
VLT FC New Generation D-Frame, housing size D5h / D6h
For use with floor installation / assembly of the VLT in IP21 / 54.
Contains components / assembly parts and fastening material"
176F3522 kit,cooling,in bottom out back,d1h d3h
176F3523 kit,cooling,in bottm out back,ss,d1h d3h
176F3526 kit,cooling,in back out back,3r,weld,d4h
176F3528 kit,cooling,in bottm out back,ss,d2h d4h "Cooling air entry bottom / Cooling air exit top
For frame-sizes D2h and D4h"
176F3534 kit,f18,lhd,ip54,backwall cooling
176F3538 kit,e9,lhd,ip54,backwall cooling
176F3539 kit,pedestal,200mm,d7h d8h kit,pedestal,200mm,d7h d8h
176F3627 Cooling Kit, in btm/ out top, 1800, D3h
176F3632 Pedestal Kit, 400mm, D2h "Sub-base kit, H 400 mm for VLT FC New Generation
D-Frame, housing size D2h. For use with floor
installation / assembly of the VLT in IP21 / 54.
Contains components / assembly parts and fastening material"
176F3648 Cooling Kit, in back/out back, D1h
176F3656 Cooling Kit, in back/out back, SS, D1h
176F3711 Current Transformer, AAF, 500A, 3pcs
176F3712 Current Transformer, AAF, 1000A, 3pcs
176F3713 Current Transformer, AAF, 1500A, 3pcs
176F3730 Ethernet adapter kit, D, E
176F3810 KIT,MULTI WIRE,MOTOR,BB,D2H,D4H,P454
176F3811 KIT, COMMON MODE, T5/100M or T7, P454
176F3812 KIT,MULTI WIRE,MOTOR,BB,D1H,D3H,P454
176F3817 KIT, MULTI WIRE, D1H, P454