3kW 230V Single-Phase Input VFD for a Hotel Booster Pump

3kW 230V Single-Phase Input VFD for a Hotel Booster Pump

AUSENIST 3kW 230V single-phase hotel booster pump VFD solution

Engineering reference image; final wiring and model selection depend on the project data.

A 3kW hotel booster pump can run from a 230V single-phase input VFD when the pump motor is a compatible three-phase 220–230V motor and the drive output current covers the motor nameplate current. The VFD output is three-phase; a single-phase pump motor is not automatically suitable.

Recommended Configuration

Item Reference Selection
Motor 3kW, three-phase, 220–230V
Input 220–230V single-phase
Output 220–230V three-phase
Pump Vertical multistage booster pump
Control Constant-pressure PID
Sensor 4–20mA pressure transmitter
VFD AUSENIST 230V-class pump VFD, selected by current

What Must Be Confirmed?

  • Motor voltage, current, frequency and star/delta connection.
  • Maximum hotel demand, static head and target pressure.
  • Sensor range and installation point.
  • Input breaker, cable capacity and supply-voltage stability.
  • Whether one pump or a duty/standby pair is required.

Selection Logic

Do not select by 3kW alone. Compare the motor rated current with the VFD continuous output current. Single-phase input current is higher than the three-phase motor line current, so the feeder and breaker need a separate check. Enter the motor nameplate data, scale the pressure sensor correctly, and use gradual acceleration to limit pipe shock.

Common Mistakes

  • Connecting a 380V-only motor to a normal 230V-class VFD.
  • Assuming the output is single-phase because the input is single-phase.
  • Ignoring the high current drawn from the 230V feeder.
  • Using a pressure setpoint without checking the pump curve.

AUSENIST Solution

AUSENIST can match the drive current, preset PID and protection parameters, and support pump-mounted or OEM configurations. This solution is unsuitable until the motor winding voltage and available input capacity are verified.

FAQ

Can it run a 230V single-phase motor?

Not by default. This reference design is for a compatible three-phase motor.

Is a pressure tank still useful?

A small correctly selected tank can reduce rapid pressure changes and frequent wake cycles.

What information is needed for a quotation?

Send the motor nameplate, pump curve, required pressure, supply details and quantity.

Related AUSENIST Pages

Send us your motor nameplate and hotel pressure requirement. AUSENIST can recommend the VFD model and basic parameter configuration.

PREVIOUS:440V and 460V Water Pump VFD Selection

NEXT:380V Three-Phase Water Pump VFD Selection